Construction
| Component |
Specification |
| Conductor |
Electrolytic annealed tinned copper, class 5 (flexible) according to IEC 60228 and EN 60228. |
| Insulation |
Halogen-free cross-linked rubber according to table B1 in Annex B of EN 50618 and IEC 62930. |
| Outer sheath |
Halogen-free cross-linked flexible rubber according to table B1 in Annex B of EN 50618 and IEC 62930. Available in red or black color. |
Characteristics
Electrical performance
| Feature |
Specification |
| Low voltage |
1.5 (1.8) kV DC, 1.0/1.0 kV AC. |
Thermal performance
| Feature |
Specification |
| Maximum conductor temperature |
90°C (120°C during 20,000 h). |
| Maximum short-circuit temperature |
250°C (max. 5 s). |
| Minimum service temperature |
-40°C (fixed and protected installations). |
Fire performance
| Feature |
Specification |
| Flame non-propagation |
According to EN 60332-1-2 / IEC 60332-1-2. |
| Fire non-propagation |
According to EN 50399. |
| Reaction to fire CPR |
Cca-s1b, d2, a1 according to EN 50575. |
| Low smoke halogen free |
According to EN 60754-1 / IEC 60754-1. |
| Low corrosive gases emission |
According to EN 60754-2 / IEC 60754-2. |
| Low smoke emission |
According to EN 61034 / IEC 61034: Light transmittance > 60%. |
Mechanical performance
| Feature |
Specification |
| Minimum bending radius |
- 4x cable diameter (cable diameter ≤ 8 mm)
- 5x cable diameter (8 < cable diameter ≤ 12 mm)
- 6x cable diameter (cable diameter > 12 mm)
|
| Impact resistance |
AG2 Medium severity. |
Environmental performance
| Feature |
Specification |
| Chemical & Oil resistance |
Excellent. |
| Grease & mineral oils resistance |
Excellent. |
| Ozone resistant |
According to EN 50618. |
| UV Resistant |
According to EN 50618 and IEC 62930. |
| Water resistance |
AD7+ Immersion. ADB Submersion. |
Installation conditions
| Condition |
Details |
| Open Air |
Suitable |
| Buried |
Suitable |
| In conduit |
Suitable |