| Component | Specification |
|---|---|
| Conductor | Aluminium class 2 according to EN 60228 and IEC 60228. |
| Insulation | Cross-linked polyethylene, type XLPE according to IEC 60502-1. The standard identification of insulated conductors according to HD 308 is the following:
|
| Outer sheath | Special UV resistant PVC, type ST2 according to IEC 60502-1. Black colour. |
Characteristics
Electrical performance
| Feature | Specification |
|---|---|
| Low voltage | 1.5/1.5 (1.8) kV DC according to EN 50618. 1.8/3 (3.6) kV AC according to IEC 60502-1. |
Thermal performance
| Feature | Specification |
|---|---|
| Maximum conductor temperature | 90°C |
| Maximum short-circuit temperature | 250°C (max. 5 s). |
| Minimum service temperature | -40°C (fixed and protected installations). |
| Minimum installation and handling temperature | 0°C (on cable surface). |
Fire performance
| Feature | Specification |
|---|---|
| Flame non-propagation | According to EN 60332-1 / IEC 60332-1. |
| Reaction to fire CPR | Eca according to EN 50575. |
| Reduced halogen emission | Chlorine < 15%. |
Mechanical performance
| Feature | Specification |
|---|---|
| Minimum bending radius | 5x cable diameter. |
| Impact resistance | AG2 Medium severity. |
Environmental performance
| Feature | Specification |
|---|---|
| Chemical resistance | Good. |
| Grease & mineral oils resistance | Good. |
| UV Resistant | According to EN 50618 and HD 605/A1. |
| Water resistance | AD8 Submersion. |
Installation conditions
| Condition | Details |
|---|---|
| Open Air | Suitable |
| Buried | Suitable |
| In conduit | Suitable |